Input data (DC) | |||||
Max.recommended PV power (for module STC) | 12000W | 12000W | 13500W | 15000W | |
Max.DC voltage | 600V | 600V | 600V | 600V | |
Start voltage | 80V | ||||
Nominal voltage | 360V | ||||
MPP voltage range | 60V-550V | 60V-550V | 60V-550V | 60V-550V | |
Max.input current per MPP tracker | 16A | ||||
Max.short-circuit current per MPP trackers | 24A | ||||
Output data (AC) | |||||
AC nominal power | 7000W | 8000W | 9000W | 10000W | |
Max.AC apparent power | 7000VA | 8000VA | 9000VA | 10000VA | |
AC grid frequency(tange*) | 50/60 Hz(45-55Hz/54-65 Hz) | ||||
Max.output current | 33.5A | 38.3A | 43A | 45.5A | |
Nominal AC voltage(tange*) | 220V | ||||
Adjustable power factor | 0.8leading…0.8lagging | ||||
AC gnid connection type | Single phase | ||||
Efficiency | |||||
Max.efficiency | 98.1% | ||||
European efficiency | 97.5% | ||||
MPPT efficiency | 99.5% | ||||
Protection devices | |||||
DC reverse polanty protection | Yes | ||||
DC switch | Yes | ||||
AC short-circuit protection | Yes | ||||
Ground fault monitoring | Yes | ||||
Grid monitoring | Yes | ||||
Anti-islanding protection | Yes | ||||
Residual-current monitoring unit | Yes | ||||
AFCI protection | Optional | ||||
General data | |||||
Dimensions (W/H/D) | 425/387/180mm | ||||
Weight | 20kg | ||||
Operating temperature range | -25ºC…+60ºC | ||||
Altitude | 4000M | ||||
Self-Consumption night | <1W | ||||
Topology | Transfomerless | ||||
Cooling | Natural convection | ||||
Protection degree | IP66 | ||||
AC connection |
Cable gland +OT terminal
|
||||
Display | OLED+LED | ||||
Interfaces:RS485/USB/Wi-Fi/ GPRS/RF/LAN | Yes/Yes/Optional/Optional/Optional /Optional | ||||
Warranty:5 years/10 years | Yes /Optional | ||||
IEEE1547,UL1741, Inmetro, G99,EN50549-1,UNE217001, UNE206007, PO12.2
|